Direct-On-Line Starter

Engineering/Technical

The simplest form of motor starting, in which the full supply voltage is applied directly to the motor terminals at the moment of starting by closing a contactor, without any intermediate voltage reduction; used for motors up to approximately 11 kW (or higher, subject to the supply system's capacity and the generator voltage dip it can tolerate) where the high starting current — typically 6–8 times rated current — and starting torque shock are acceptable. DOL starters consist of a main contactor, a thermal overload relay, a control circuit with start/stop pushbuttons, and a local/remote selector switch, and are the most robust and lowest-cost starter configuration available.