Earth Continuity Test

Engineering/Technical

A low-resistance measurement test that verifies the integrity of the protective earthing path between the exposed metal casing or frame of an electrical machine or switchgear and the ship's hull earth connection, confirming that a fault current due to insulation failure would be safely conducted to earth through the protective conductor rather than through a person touching the equipment. The test is performed with a low-voltage, high-current test instrument that measures the resistance between the equipment's earth terminal and a known earth point; a resistance above 0.1 Ω (or the relevant standard's limit) indicates a broken, corroded, or missing earth conductor that must be repaired before the equipment is re-energized.