Power Factor Correction

Engineering/Technical

The deliberate introduction of capacitive reactive power (kVAR leading) into an electrical system to compensate for the lagging reactive power drawn by inductive loads, raising the system power factor toward unity and reducing the total apparent current (kVA) that generators and cables must deliver for a given amount of useful work (kW). On ships, power factor correction is achieved by connecting capacitor banks at the main switchboard or at individual large motor terminals; the degree of correction is carefully managed to avoid over-correction (leading power factor) that can cause voltage rise and reverse reactive power relay operation, and to avoid resonance between the capacitance and system inductance at harmonic frequencies.