An indicating instrument fitted on the main switchboard that displays the rate and direction of frequency difference between an incoming generator and the live busbars, with the pointer rotating clockwise when the incoming machine runs faster than the bus and counter-clockwise when it runs slower, and coming to rest at the twelve o'clock position when the two frequencies are exactly equal (synchronism). The circuit breaker is closed when the pointer is at or just approaching twelve o'clock from the slow side, ensuring the generator takes on a small positive load immediately on connection rather than immediately demanding reverse power from the bus.
Synchroscope