A motor protection device whose bimetallic strip or electronic heating element carries the motor running current and deflects or trips its contacts when the thermal equivalent of the current exceeds the relay's set current rating multiplied by its time-current characteristic, simulating the thermal heating of the motor winding and tripping the motor's contactor to prevent overheating damage. The relay has a settable current range calibrated to the motor's full-load amperes, a reset mechanism (manual or automatic), and a phase-failure sensing feature that trips on loss of any phase regardless of the total current level.