Voltage Imbalance

Engineering/Technical

An asymmetry in the three-phase supply voltage in which the three phase voltages are not equal in magnitude or are not displaced exactly 120° apart in phase angle, typically caused by unequal single-phase loading between the three phases, an open-circuit fuse on one phase, or a generator with an imbalanced excitation or winding fault. Voltage imbalance causes negative-sequence currents to flow in three-phase induction motors, which produce a braking torque opposing the positive-sequence torque and generate additional heat in the rotor; a voltage imbalance of 2 % can reduce motor output capacity by approximately 10 %, and the motor manufacturer's de-rating curve must be consulted whenever imbalance is measured.